ExGo Remote Status IndicatorRemote Status Indicator

The Ex Remote Status Indicators are available in two formats, a basic display only with optional key switches or a manual release version with optional keyswitch for automatic/manual mode.

The Ex-extinguishing system detects a fire in the same manner as a fire alarm system, but in addition to sounding alarms, it also controls the release of an extinguishing agent.

The extinguishing agent can take many forms from CO² through to specialist gasses developed solely for extinguishing purposes. The agent is released into the atmosphere in the area where a fire has been detected reducing the density of oxygen in the atmosphere around the fire, thus extinguishing the fire.

The Ex-extinguishing system is used primarily in areas of significant value/strategic importance to businesses e.g. computer suites, telecom switch-rooms thus providing a cost effective solution to protect your work place.


Features

  • Small and compact
  • RS485 network port
  • Optional manual release or display only
  • Surface mount or semi-flush option
  • Up to 7 remote status indicators per one ExGo 1 loop panel
  • 3 year warranty as standard
  • Key switch option for mode select or enable controls
  • Multiple languages
  • Programmable inputs & outputs


Key Features

Large graphical LCD displayLogo programming softwareSlide in labels24v DC supply
Alpha-numeric keypad3 Year warranty as standardRS-485 networkSmall & compact
Specification
EnclosureSteel IP30 (optional IP65 version available upon request)
Dimensions (HxWxD mm)190 x 235 x 45
Environmental classClass A - indoor IP30 0°C to 40°C
Humidity95% max
Weight (excluding batteries)1.5Kg
Cable entries (20mm knockouts)4x top and 4x bottom rear
Power supply24V DC nominal (18V - 28V
Relay outputs (optional)2x rated at 1A 30 V AC/DC (max) 10mA 5V (min) programmable (requires EXP-007F)
Key switches 1 x programmableEx-3021 & Ex-3031 - Fitted
Manual releaseEx-3020 & Ex-3021 - No; Ex-3030 & Ex-3031 - Yes
External inputs (monitored)2 x programmable
CommunicationsRs485 to Ex-3000 series control panel
DisplayGraphic LCD 124 x 64 pixels
LED indicators12 in Total, Fire, Release, Timer, Disablement, Mode and Fault indications.

Order Codes and Options

Ex-3020: RSI c/w LCD + LED indicators
Ex-3021: RSI c/w LCD + LED indicators with mode select key switch
Ex-3030: RSI c/w LCD + LED indicators with manual release button
Ex-3031: RSI c/w LCD + LED indicators with MR button and mode select key switch
Exm-002: Semi-flushing bezel for RSI
Exp 001: Enable controls (trapped) key switch assembly
Exp 002: Mode select (un-trapped) key switch assembly
Exm-002: Semi-flushing bezel
Exp-007F: 2-Way Relay Card (Fitted)