ExGo EOL ModuleEOL Module

The Zone Active end-of-line Module provides active end-of-line monitoring for zone circuits fitted with detector diode bases in accordance with BS5839-1

The module will create a fault condition on the panel if a detector is removed from its base, without affecting the remainder of the zone.

Specification
Dimensions H x W x D mmOverall: 27 x 20 x 7(max)
End-of-line resistance6800 Ohms
Environmental classIndoor 0°C to 40°C
Humididty95% Max
Operating voltage17-30V DC
Zone voltage20V DC typical

Order Codes and Options

Exp-006: Zone active End of Line (pack of 5)

Compatibility

Compatible with the ExGo Series Gas Extinguishing Panel input circuits.

Limitations

For use in gas extinguishing installations where an EOL module is required.