- 1,2,or 4 loop formats
- Each 500mA digital signaling line circuit support up to 126 intelligent devices
- 1,000 Fire Zones when networked or 200 per panel
- Easy, high performance networking (up to 200 nodes)
- Circuit monitoring from any panel or annunciator
- True peer to peer networking
- Style 4 or 7 configuration
- Individual node configurable event reporting and control
- Comprehensive network diagnostics
- Compatible with all of the AX Series peripherals including annunciators, relay modules, I/O modules, power supplies, internal and portable printers, network modules, LED/switch modules, modem, RS-232, amplifiers, DACT and more
- Supports shielded wire, non-shielded wire and fibre optic lines
- Beam detectors, smoke detectors, sounder bases, open area sounders and beacons can be powered from SLC without need for a separate 24V supply
- Superb noise immunity and emissions
- Regulated loop voltage sustained during AC loss 2 or 4 voltage regulated NACs compatible with most listed NAC devices
- Two Amp current limit per NAC with alerts on panel or via email if limit exceeded
- Advanced’s Simple Select & Click programming & configuration
|
- Panel includes large 240x60 backlit LED with
- Advanced’s simple navigation and programming
- Unique, built-in voltage and current meters for easy diagnostics can be viewed on panel or remotely.
- Unique auto-test of battery cell integrity
- Direct USB and RS232 PC connections or Remote access and control of panels and network via Advanced ipGateway
- Output fully regulated clean 24 volts DC to all Notification Appliance Devices, making the panels ideal for retrofit applications without fear of failing regulatory compatibility listings
- 100% digital communications on the SLC to all intelligent smoke detectors and I/O modules
- Fast response and superior rejection of unwanted RF noise.
- Multi-sensor programming options allow for supervisory pre-alarm upon programmable smoke obscuration and fire alarm upon programmable temperature fixed or rate of rise.
- Fully integrated 40/80 Watt digital audio options
- Autolearn and Loop detection
- Quick start and protect - A working system after an Auto learn is performed Ul864 ‘9th Edition’ approved
|