Axis ENBMS/Graphics Interface

The BMS/Graphics Interface interface allows BMS systems and graphical PCs to be integrated with the Axis EN series of fire control panels and remote terminals.

The interface is an integral part of the Ad- Net network, permitting the handling of all network traffic and event prioritisation, via a PC, using a simple RS232 connection.

Multiple interfaces can be connected to the network catering for sites requiring control from a number of graphical PCs.

Applications

Provides connection to various 3rd party graphics systems.

Key Features

  • Sector based programming
  • Each BMS interface is individually programmable with the available dynamic cause and effects rules
  • Standard & fault tolerant network versions
  • Easily configured via PC-NET-003
  • 3 year warranty as standard
Specification
Supply Voltage Input18-28V DC
Operating Temperature-5°C to 50°C
Relative Humidity95% non-condensing (maximum)
PCB Dimensions H x W x D mm88 x 242 x 18
Weight75 grams
IndicationsOn-board LED indicators for heartbeat, network Rx/Tx and RS232 Rx/Tx
Supply CurrentStandard 48mA (/FT 86mA) at 24v DC
Serial InterfaceIsolated RS232 interface for BMS/PC
Fault InputMonitored volt free clean contact
Enclosure Dimensions H x W x D mm218 x 300 x 45
Enclosure Weight2 Kg

Order Codes and Options

Mxp-510-BX: Standard Network BMS Interface Boxed
Mxp-510-BX/FT: Fault-Tolerant Network BMS Interface Boxed
Mxp-510: Standard Network BMS Interface (Card only)
Mxp-510/FT: Fault Tolerant network BMS interface (Card only)

Compatibility

Can be used with any Ad-NeT or Ad-NeT+ network series control panels.