Programming tip: Cause and effect checker

Do you want confirmation that your programming is correct when using our configuration software? If so, you can use the “Cause and Effect Check” option that's built into our programming software. This allows you to confirm the outcome of an individual device activation. The results displayed will vary depending whether an input or output is […]

Default Service Due Date

Is the default Service Due Date on your panel set to a date in the near future? If so, the panel will enter a fault condition when this date is reached to alert the site operator that a service visit is overdue. To pre-empt this and prevent your panel going into fault, you can set […]

One man walk test

The one man walk test feature on all Advanced panels provides a 10-second activation in which sounders will automatically silence. By default, relays do not operate. You can extend the duration of the 10-second activation up to a maximum of 60 seconds using the MxPro and Axis EN PC config tool. This is ideal for […]

Fix data corruption faults with Trace Logging Mode

The Advanced ‘Trace Logging Mode’ can track, trace and fix those niggling data corruption faults that sometimes arise from the following installation issues: Induced Alternating Current (AC) Earth Fault Earth Potential Difference Water Ingress Faulty Device Multi-Core Cable The Trace Logging option has three different operating modes: Standard, Standard+ and Diagnostic, which you can enable […]